5.13.1 Cable Trays
a) cable tray, elbow, T-shaped connector, such as the annex to be completed in the factory. Cable tray
Required by the hot dip plating, and the Bo-hole plate made of quality.
b) install the tray when the tray was cut to be applied in cutting the Agency for the protection of zinc-containing paint.
c) pallets to be a certain strength and rigidity to protect the installation of the cable tray.
d) not appear detrimental to the cable tray cable insulation and protection layer of the sharp edge convex or prominent stria
Part, so as to avoid damage to cable insulation and protection layer.
e) to install cables in the cable tray before the tray to be completely cleared of debris.
Diameter, wall thickness
26mm 3.5mm
32mm 3.5mm
42mm 4.0mm
55mm 4.0mm

30
f) the top of the cable tray to be enough space left to facilitate cable installation and maintenance. When the cable care
Set to fly in under the ceiling, wall or structure of the wall must have been approved in the hot-dip galvanized steel
Support bracket or hook.
g) When the cable with other professionals operating in parallel, the stent should be used to support a dedicated cable tray.
h) when the two intersect vertical cable tray should be used outside the connector or junction piece in order to avoid access
Any point on the situation down or bending. Outside the connector or splice film should be the minimum to 2
Round rust-proof screws installed in each cable tray within the tray to the fixed junction.
i) all the bending and a T-connected spaces there should be a minimum bend radius of 50mm. Cable tray of
By bending should be allowed to carry the largest cable bend radius, or in line with the "low-voltage distribution
Design specifications "GB50054-1995 and" civil electrical design specifications "JGJ/T16-
1992 within the stipulated limit bend radius.
j) the entire cable tray should be strong to be installed at the building structure, the tray should be separated by the structure of the smallest
13mm distance.
k) should be separated by a fixed support and adequate support from the cable tray, especially in curved spaces and T-then
I position.
l) when the cable tray through the structure of the mobile / expansion of contacts, the tray should be the physical separation, the separated
Distance should be mobile / expansion of the distance between the cracks or more. In order to maintain the continuity of grounding should be 1
Gen-150mm ² copper conductor across the gap soft and firmly connected at both ends of the tray.
m), such as cable tray need to pass through, or across the edge of tray shall be low smoke zero halogen ring or packaging
売outside the protection of cable from the sharp edge of harm to donate.
n) when the cable through the walls of the hole, to be equipped with supporting accessory tray to support the cable over the wall.
o) the need for all cable tray back side (return-edge).