Miniature circuit breakers and molded case circuit breakers special requirements

    

a) miniature circuit breaker to be in line with the "Code for Design of Low Voltage Distribution" GB50054-1995 requirements,
The requirements of BS EN60898 and with C-type release characteristics. Molded Case Circuit Breaker subject
"Code for Design of Low Voltage Distribution" GB50054-1995 requirements, BS EN60947-2's
Requirements, selection of B-type circuit breakers. Both magnetic circuit breaker for terminal type.
b) more than when the current in the 60A, MCCB instantaneous circuit protection devices to be adjustable帧长
Whole.
c) Current leakage protection required for the action type.
d) if not specified, miniature circuit breakers rated breaking capacity not less than 6kA, molded case circuit
Device breaking capacity not less than 22kA.
e) the use of miniature circuit breaker distribution board will be subject to the "low-voltage power distribution design specifications" and BS EN
The requirements of 604,393.
f) miniature circuit breaker for the maximum rated current 100A.
g) MCB polar components required for joint and internal interlock in order to ensure than any one phase
When the circuit breakers contained polar solution can be deducted immediately. Circuit breakers in the installation of three unipolar can not
Mechanical bundled.
h) the protection of distribution lines to all devices to be equipped with sufficient capacity to ensure that: First of all, the over-current protection
Care to protect equipment; the second, when the switch in any mode, or for power supply bypass, the
Switching surge and transient voltage lines would not lead to the solution of logical deduction; otherwise, must be allocated
Preparation of appropriate surge suppression devices, in line with the "low-voltage power distribution design specifications" within the standards,
IEC61643 1, IEC61051 1 or related recognized standards in order to avoid equipment affected by these
Current or affected by the instantaneous voltage.